Balancing and Settlement Code
BSC PROCEDURE
Technical Assurance of Half Hourly Metering Systems for Settlement Purposes
BSCP27
Date: |
Intellectual Property Rights, Copyright and Disclaimer The copyright and other intellectual property rights in this document are vested in Elexon or appear with the consent of the copyright owner. These materials are made available for you for the purposes of your participation in the electricity industry. If you have an interest in the electricity industry, you may view, download, copy, distribute, modify, transmit, publish, sell or create derivative works (in whatever format) from this document or in other cases use for personal academic or other non-commercial purposes. All copyright and other proprietary notices contained in the document must be retained on any copy you make. All other rights of the copyright owner not expressly dealt with above are reserved. No representation, warranty or guarantee is made that the information in this document is accurate or complete. While care is taken in the collection and provision of this information, Elexon Limited shall not be liable for any errors, omissions, misstatements or mistakes in any information or damages resulting from the use of this information or action taken in reliance on it. |
Version | Date | Description of Changes | Changes Included | Mods/ Panel/ Committee Refs |
1.0 | 01/06/04 | New BSCP (This BSCP supersedes BSCP526 and BSCP26) | CP998 |
|
2.0 | BETTA Effective Date | BETTA 6.3 and SVA February 2005 Release | CP1091 and BETTA 6.3 | SVG/48/004 |
3.0 | 02/11/05 | CVA Nov 05 Release | CP1062 version 1 | SVG/56/014 |
4.0 | 22/02/07 | Reformatted and Changes for CP1176 Updated following industry review | CP1164 CP1172 CP1176 | SVG/68/04 ISG/69/01 ISG/66/06 SVG/66/04 ISG/68/002 SVG/67/002 |
5.0 | 23/08/07 | P197 Release | P197 |
|
6.0 | 01/11/07 | November 07 Release | CP1195 | ISG77/03 SVG77/04 |
|
|
| CP1210 | ISG79/02 SVG79/02 |
7.0 | 28/02/08 | February 08 Release | CP1212 | ISG81/01 SVG81/01 |
8.0 | 26/06/08 | June 08 Release | CP1223 | SVG84/02 ISG84/01 TDC109/01 PAB84/11 |
9.0 | 26/11/08 | P207 Release | P207 | ISG91/01 SVG91/06 |
10.0 | 25/06/09 | June 09 Release | CP1265 | ISG97/01 SVG97/01 |
11.0 | 24/06/10 | June 10 Release | CP1324 | ISG111/03 |
12.0 | 29/03/2013 | 29 March 2013 | CP1379 | PAB135/07 ISG139/01 SVG141/06 |
13.0 | 27/02/2014 | February 2014 Release | CP1393 | PAB152/05 ISG149/07 SVG152/06 |
14.0 | 26/02/2015 | February 2015 Release | ORD0051 | Secretary of State |
15.0 | 05/11/2015 | November 2015 Release | P319 Self-Governance | Panel 239/07 |
16.0 | 30/06/2016 | June 2016 Release | CP1454 | ISG179/01 SVG182/02 |
17.0 | 03/11/2016 | November 2016 Release | CP1463 | ISG184/06 SVG187/02 |
18.0 | 22/02/2018 | February 2018 Release | CP1490 | ISG197/05, SVG199/04 |
19.0 | 29/03/2019 | 29 March 2019 Standalone Release | P369 | P285/12 |
20.0 | 27/02/2020 | February 2020 Release | P391 Self-Governance | P295/08 |
21.0 | 01/09/2021 | 1 September 2021 Non-Standard Release | P420 | P316/05 |
22.0 | 04/11/2021 | 4 November 2021 Standard Release | CP1545 | ISG244/02 SVG246/04 |
CVA Metering Systems | SVA Metering Systems |
|
|
CVA Metering Systems | SVA Metering Systems |
BSCP02 – Proving Test Requirements for CVA Metering Systems | BSCP11 –Trading Disputes |
BSCP06 – CVA Meter Operations for Metering Systems Registered in CMRS | BSCP32 - Metering Dispensations |
BSCP11 –Trading Disputes | BSCP501 - Supplier Meter Registration Service |
BSCP20 – Registration of Metering Systems for Central Volume Allocation | BSCP502 – Half Hourly Data Collection for SVA Metering Systems Registered in SMRS |
BSCP32 – Metering Dispensations |
|
BSCP537 – Qualification Process for SVA Parties, SVA Party Agents and CVA MOAs | BSCP515 – Licensed Distribution |
BSCP538 – Error and Failure Resolution | BSCP537 – Qualification Process for SVA Parties, SVA Party Agents and CVA MOAs |
BSCP601 - Metering Protocol Approval and Compliance Testing | BSCP538 – Error and Failure Resolution |
| BSCP550 - Shared SVA Meter Arrangement of Half Hourly Import and Export Active Energy |
| BSCP601 - Metering Protocol Approval and Compliance Testing |
Ensure that an appropriate person is in attendance when requested by the Registrant
Provide all requested information (including measurement transformer certificates)
Perform all actions to rectify a non-compliance
Provide adequate evidence of rectified non-compliance to the TAA.
Previous non compliances;
Information provided by the BSC Auditor;
Technical Assurance of Performance Assurance Parties checks;
Line Loss Factor Audits;
Information from Parties;
Performance related issues;
Settlement error;
Information provided by its sub-committees; or
Information provided by the Panel.
Site name
Site address
Site telephone number
Circuit Identifier
Applicable CoP (including the specific Issue)
Current applicable Metering Dispensation(s)
Meter Calibration Certificates
Current Transformer Test Certificates (including details of manufacturer, type, serial number and class).
Voltage Transformer Test Certificates (including details of manufacturer, type, serial number and class).
Applicable Meter Compensation values (including evidence to support the applied values).
This list is not exhaustive and any relevant information that may help the TAA obtain access to all the Metering Equipment should be made available to the TAA.
NC | A non-compliance has been identified through the Consumption Data Comparison Check that is deemed to be currently affecting the quality of data for Settlement purposes. |
Category 1 Non Compliance | A non-compliance has been identified from an Inspection Visit, which is deemed to be currently affecting the quality of data for Settlement purposes |
Category 2 Non Compliance | A non-compliance has been identified from an Inspection Visit, which is deemed to have the potential to affect the quality of data for Settlement purposes |
Category A Non Compliance | A non-compliance has been identified from an Desktop Audit, which is deemed to be currently affecting, or has a high likelihood of affecting, the quality of data for Settlement purposes |
Category B Non Compliance | A non-compliance has been identified from a Desktop Audit, which has been deemed to have a lower likelihood of affecting the quality of data for Settlement purposes, or for the non-provision of evidence |
Observation | A non-compliance has been identified which is deemed neither to affect nor to have the potential to affect the quality of data for Settlement purposes |
BSC | Balancing and Settlement Code (The “Code”) |
BSCCo | Balancing and Settlement Code Company |
BSCP | BSC Procedure |
CDCA | Central Data Collection Agent |
CMRS | Central Meter Registration Service |
CoP | Code of Practice |
CSD | Code Subsidiary Document |
CT | Current Transformer |
CVA | Central Volume Allocation |
CVA MOA | Central Volume Allocation Meter Operator Agent |
HH | Half Hour |
HHDC | Half Hourly Data Collector |
HV | High Voltage |
LDSO | Licensed Distribution System Operator |
LV | Low Voltage |
MOA | Meter Operator Agent |
MSID | Metering System ID |
MTD | Meter Technical Details |
NETSO | National Electricity Transmission System Operator as the holder of the Transmission Licence and any reference to “NETSO”, “NGESO”, “National Grid Company” or “NGC” in the Code or any Subsidiary Document shall have the same meaning. |
PAA | Performance Assurance Administrator |
PAB | Performance Assurance Board |
PAP | Performance Assurance Party (Includes Registrants and Party Agents) |
REM | Risk Evaluation Methodology |
RER | Risk Evaluation Register |
ROP | Risk Operating Plan |
SCoP | Scottish Code of Practice (for Metering Systems registered in Scotland prior to the BETTA Effective Date) |
SMRA | Supplier Meter Registration Agent |
SMRS | Supplier Meter Registration Service |
SVA | Supplier Volume Allocation |
SVA MOA | Supplier Volume Allocation Meter Operator Agent |
TAA | Technical Assurance Agent |
VT | Voltage Transformer |
WD | Working Day |
The MSID relating to the applicable SVA or CVA Metering System; and
The nature of the non-compliance.
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.1.1 | As specified in section 1.9 | Request Metering System Ids and associated information. | BSCCo | CDCA | Relevant information from HH Metering System Id, GSP Group, Registrant, MOA, HHDC and Measurement Class. | Email or as agreed |
3.1.2 | As specified in section 1.9 | Request Metering System Ids and associated information. | TAA | SMRA | Relevant information from HH Metering System Id, GSP Group, Registrant, MOA, HHDC and Measurement Class. | Email or as agreed |
3.1.3 | Within 10 WD of request in 3.1.1 | Provide Half Hourly Metering System Ids and associated information. | CDCA | BSCCo | Relevant information from HH Metering System Id, GSP Group, Registrant, MOA, HHDC and Measurement Class. | Email or as agreed |
3.1.4 | Within 10 WD of request in 3.1.1 | Provide Half Hourly Metering System Ids and associated information. | SMRA | TAA | Relevant information from HH Metering System Id, GSP Group, Registrant, MOA, HHDC and Measurement Class. | Email or as agreed |
3.1.5 | Upon receipt of data in 3.1.3 | Provide the TAA with the data. | BSCCo | TAA | Lists of HH Metering System Ids and associated Registrant and MOA. | Email or as agreed |
3.1.6 | Within 10 WD of receipt of data in 3.1. 4 and 3.1.5 | Randomly select 10% more Metering Systems than will be audited, as agreed by BSCCo. Finalise sample of HH Metering System to avoid bias towards any one party or type of Metering Equipment and derive inspection and Desktop Audit schedule. Proceed to Section 3.6 (Inspection Visit) or Section 3.7 (Desktop Audit) | TAA |
| Lists of HH Metering System Ids and associated Registrant and MOA. | Internal process |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.2.1 | At PAB meeting | Agree and notify BSCCo of the size and scope of the Desktop Audit Sample. | PAB | BSCCo | Number of Desktop Audits to be completed in the audit year and the scope of the audit. | PAB Paper: Risk Operating Plan |
3.2.2 | Within 5 WD of 3.2.1 | Confirm to the TAA, the size and scope of the Desktop Audit Sample. | BSCCo | TAA | Number and type of each Metering System to be audited via desktop. | Email or as agreed |
3.2.3 | If required (as directed by BSCCo), within 10 WD of. 3.2.2 | Request information from each Registrant, MOA and LDSO for all relevant Metering Systems to be audited via desktop. | TAA BSCCo (as appropriate) | Registrant, LDSO (or NETSO) and MOA HHDC/CDCA (as appropriate) | Information about Metering Systems to be audited via desktop as requested. | Email or as agreed |
3.2.4 | If required (as directed by BSCCo), within 20 WD of receipt of request at 3.2.3 | Provide information on all Metering Systems as requested. | Registrant, LDSO (or NETSO) and MOA HHDC/CDCA (as appropriate) | TAA BSCCo (as appropriate) | Information about Metering Systems to be audited via desktop as requested. | Email or as agreed |
3.2.5 | Upon on receipt of information (if required) | BSCCo will provide this information to the TAA. | BSCCo | TAA | Information about Metering Systems to be audited via desktop as requested. | Email or as agreed |
3.2.6 | Upon receipt of information or as directed by BSCCo | Randomly select the agreed number of each type of Metering System which comprises the agreed Desktop Audit Sample. Proceed to Section 3.7. | TAA |
| Select sample as instructed by BSCCo. | Internal process |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.3.1 | At PAB meeting | Agree and notify BSCCo of Specific Sample. | PAB | BSCCo | Number and type of each Metering System to form Specific Sample. | PAB Paper: Risk Operating Plan |
3.3.2 | Within 5 WD of 3.3.1 | Confirm to the TAA, the Specific Sample. | BSCCo | TAA | Number and type of each Metering System to form Specific Sample. | Email or as agreed |
3.3.3 | Within 10 WD of . 3.3.2 | Request information from each Registrant, SVA MOA and LDSO for all relevant Specific Sample Metering Systems registered in SMRSs. | TAA BSCCo (as appropriate) | Registrant, LDSO (or NETSO), MOA and HHDC/CDCA (as appropriate) | Information about Specific Sample Metering Systems as requested. | Email or as agreed |
3.3.4 | Within 20 WD of receipt of request at 3.3.3 | Provide information on all Specific Sample Metering Systems as requested. | Registrant, LDSO (or NETSO), SVA MOA and HHDC/CDCA (as appropriate) | TAA BSCCo (as appropriate) | Information about Specific Sample Metering Systems as requested. | Email or as agreed |
3.3.5 | Upon on receipt of information | BSCCo will provide this information to the TAA. | BSCCo | TAA | Information about Specific Sample Metering Systems. | Email or as agreed |
3.3.6 | Upon receipt of information | Randomly select the agreed number of each type of Metering System which comprises the agreed Specific Sample group. | TAA |
| Select sample as instructed by BSCCo. | Internal process |
3.3.7 | At least 20 WD prior to the Inspection Visit | Request information. | TAA | SVA MOA Registrant (as necessary)
HHDC/CDCA | Meter Technical Details. Additional Metering Equipment Technical Details. Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3 Complex Site Supplementary Information Form, where applicable (SVA only). | Online database or other agreed method |
3.3.8 | Within 10 WD of receipt of request in 3.3.7 as necessary | Provide information (as necessary). | Registrant
HHDC/CDCA | TAA | Meter Technical Details. Additional Metering Equipment Technical Details. Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3Complex Site Supplementary Information Form, where applicable (SVA only). | Online database or other agreed method |
3.3.9 | On the day of the Inspection Visit or within 10 WD of receipt of TAA request in 3.3.7 | Provide information | SVA MOA | TAA | Meter Technical Details. Additional Metering Equipment Technical Details Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3Complex Site Supplementary Information Form, where applicable (SVA only) | Online database or other agreed method |
3.3.10 | Prior to Inspection Visit or Desktop Audit | Collate information required for inspection. Proceed to Section 3.6 (Inspection Visit) or Section 3.7 (Desktop Audit). | TAA |
|
| Internal process |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.4.1 | At any time | Provide information on SVA Half Hourly or CVA Metering Systems that may require a targeted Inspection Visit or Desktop Audit. | Market Participant, PAA, Panel, PAB or TAA BSCCo | BSCCo | Metering System with reasons and supporting evidence of suspected non-compliance. | Email or as agreed |
3.4.2 | Within 5 WD of receipt of information in 3.4.1 | Determine Metering System that requires a targeted Inspection Visit or Desktop Audit. | BSCCo |
| Suspected non-compliance. | Internal process |
3.4.3 | Within 1 WD of 3.4.2. | Instruct the TAA to carry out a targeted Inspection Visit or Desktop Audit and inform the TAA of the urgency. | BSCCo | TAA | Metering System and reason for targeted Inspection Visit or Desktop Audit. | Email or as agreed |
3.4.4 | At least 10 WD prior to the Inspection Visit or Desktop Audit | Request information. | TAA | MOA Registrant (as necessary)
HHDC or CDCA | Meter Technical Details Additional Metering Equipment Technical Details. Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3Complex Site Supplementary Information Form, where applicable (SVA only). | Online database or other agreed method |
3.4.5 | Within 5 WD of receipt of the request in 3.4.4 as necessary | Provide information (as necessary). | Registrants | TAA | Meter Technical Details. Additional Metering Equipment Technical Details. Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3Complex Site Supplementary Information Form, where applicable (SVA only). | Online database or other agreed method |
3.4.6 | Where CVA: Within 5 WD of receipt of TAA request in 3.3.4 Where SVA: On the day of the Inspection Visit or Desktop Audit or within 5 WD of receipt of TAA request in 3.4.4 | Provide information. | MOA | TAA | Meter Technical Details. Additional Metering Equipment Technical Details. Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3Complex Site Supplementary Information Form, where applicable (SVA only). | Online database or other agreed method |
3.4.7 | Within 5 WD of receipt of the request in 3.4.4 | Provide information. | HHDC or CDCA | TAA | Meter Technical Details. Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3Complex Site Supplementary Information Form, where applicable (SVA only). | Online database or other agreed method |
3.4.8 | Prior to Inspection Visit or Desktop Audit | Collate information required for Inspection Visit and proceed to section 3.6 Collate the information required for a Desktop Audit and proceed to Section 3.7.. | TAA |
|
| Internal process |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.5.1 | On a Quarterly basis | Identify Metering Systems that were found to be non-compliant and have since been notified as rectified. Randomly select Metering Systems agreed by BSCCo. | TAA |
| Previous inspection history. Percentages as agreed by BSCCo. | Internal process |
3.5.2 | Prior to Inspection Visit | Collate information for Inspection Visit and proceed to Section 3.6.5. | TAA |
|
| Internal process |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.6.1 | At least 20 WD4 prior to an Inspection Visit | Notify Registrant, LDSO (or the NETSO) and MOA of HH Metering System identified for Inspection Visit. | TAA | Registrant, LDSO (or NETSO) and MOA HHDC / CDCA | Date, time and Metering System to be inspected. (as detailed in Appendix 4.5.1 - BSCP27/01) | Online database or other agreed method |
3.6.2 | Within 10 WD of receipt of notification in 3.6.1. | Arrange for access to Metering System for the purposes of an Inspection Visit. | Registrant | MOA, Customer, and if necessary LDSO (or NETSO if appropriate) | Date, time and Metering System to be inspected. | Email or as agreed |
3.6.3 | At least 10 WD prior to an Inspection Visit | Notify the TAA and MOA of acceptance of impending Inspection Visit and those parties attending. | Registrant | TAA MOA | Acceptance of terms and required attendees of an impending Inspection Visit. (as detailed in Appendix 4.5.2 - BSCP27/02). | Online database or other agreed method |
3.6.4 | Where CVA: Within 10 WD of receipt of TAA request in 3.6.1 Where SVA: On the day of the Inspection Visit or within 10 WD of receipt of TAA request in 3.6.1 | Registrant, LDSO (or the NETSO), MOA to provide required information to the TAA for the purposes of the Inspection Visit. | Registrant MOA LDSO (or NETSO) | TAA | Meter Technical Details. Additional Metering Equipment Technical Details. Retail Energy Code Metering Operations Schedule Appendix 2 and Appendix 3Complex Site Supplementary Information Form, where applicable (SVA only). | Online database or other agreed method |
3.6.5 | On the day of the Inspection Visit | TAA performs Inspection Visit with MOA and LSDO (or the NETSO) in attendance, is appropriate. | TAA MOA LDSO (or NETSO) if appropriate |
|
|
|
3.6.6 | On completion of Inspection Visit Within 2 WD of completion of the Inspection Visit | TAA produces Inspection Visit findings and determines Metering System compliance. If a non compliance is identified, initiate process 3.8. If an observation is identified – notify the relevant parties If Inspection Visit is identified as compliant – notify the relevant parties. | TAA | Registrant and MOA, CDCA / HHDC, LDSO (or NETSO) if appropriate | Completed and signed Inspection Schedule | Online database or other agreed method |
3.6.7 | Within 2 WD of completion of Inspection Visit | Request current actual consumption data held by the CDCA or HHDC for the same period as recorded during the Inspection Visit. | TAA | CDCA or HHDC | Current actual consumption data held by the CDCA or HHDC for the same HH period. | Email or as agreed |
3.6.8 | Within 5 WD of receipt of request | Provide HH data requested in 3.6.7. | CDCA or HHDC | TAA | HH data. | Online database or other agreed method |
3.6.9 | Within 2 WD of receipt of 3.6.8 | TAA performs Consumption Data Comparison Check and determines Metering System compliance. If a non compliance is identified, initiate process 3.8. If an observation is identified – notify the relevant parties If Inspection Visit is identified as compliant – notify the relevant parties. | TAA | Registrant and MOA, HHDC / CDCA, LDSO (or NETSO) if appropriate | Completed, updated and signed Inspection Schedule. | Online database or other agreed method |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD | |
3.7.1 | At least 15 WD prior to a Desktop Audit | Notify and provide an Evidence Request to the Registrant, LDSO (or NETSO), MOA and HHDC/CDCA (as appropriate) of HH Metering System identified for Desktop Audit. Confirm the date that the Desktop Audit will be completed. | TAA | Registrant | Metering System to be inspected and relevant documentation as outlined in the Evidence Request (as detailed in Section 4.5.6) | Online database or other agreed method | |
3.7.2 | Within 5 WD of 3.7.1 | Commitment to provide the requested documentation and/or Consumption data, as outlined in the Evidence Request. Failure to confirm the Desktop Audit will result in a failed Desktop Audit and notification to the PAB (3.7.3) | Registrant | TAA | Acceptance of terms | Online database or other agreed method | |
3.7.3 | Within 1 WD of 3.7.2, and at least 10 WD prior to the date of the Desktop Audit | Notify and provide an Evidence Request to the, LDSO (or NETSO), MOA and HHDC/CDCA (as appropriate) of HH Metering System identified for Desktop Audit. Confirm the date that the Desktop Audit will be completed. | TAA | LDSO (or NETSO) and MOA HHDC/CDCA (as appropriate) | Metering System to be inspected and relevant documentation as outlined in the Evidence Request (as detailed in Section 4.5.6) | Online database or other agreed method | |
3.7.4 | Prior to the Desktop Audit | Provide the requested documentation and/or Consumption data, as outlined in the Evidence Request | Registrant, LDSO (or NETSO) and MOA HHDC/CDCA (as appropriate) | TAA | Acceptance of terms | Internal process | |
3.7.5 | Prior to the Desktop Audit | Collate information required for Desktop Audit. | TAA |
|
| Internal process | |
3.7.6 | On the date of the Desktop Audit specified in 3.7.1 | TAA to complete the Desktop Audit | TAA |
|
| Internal process | |
3.7.7 | Within 2 WD of 3.7.5 | TAA produces Desktop Audit findings, determines Metering System compliance and outlines follow up actions, where required. If non-compliance is identified, initiate process 3.8 and, if deemed appropriate 3.6. If an observation is identified – notify the relevant parties and, if deemed appropriate initiate 3.6. If Desktop Audit findings are identified as compliant – notify all relevant parties | TAA | Registrant, LDSO (or NETSO) and MOA HHDC/CDCA (as appropriate) | Completed, updated Desktop Audit Schedule | Online database or other agreed method |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.8.1 | Within 2 WD of completion of an Inspection Visit (3.6.5) or Desktop Audit (3.7.6) | Notify the Registrant, MOA, and HHDC/CDCA of relevant of non-compliance. If the visit was a Targeted Audit, or a Category 1 or a Category A Non Compliance has been identified, notify BSCCo. | TAA | Registrant, MOA, HHDC, CDCA; BSCCo (for Targeted Audit and Category 1 and Category A Non Compliances only) | Specific details of non-compliance (Completed and signed Inspection Schedule or Desktop Audit Schedule). | Online database or other agreed method |
3.8.1A | Within 1 WD of 3.8.1 | Notify NC, Category 1 and Category A Non Compliances | BSCCo | EMR Settlement Services provider | Details of the non-compliance including the MSID relating to the applicable SVA or CVA Metering System and the nature of the non-compliance. | Email or other agreed format |
3.8.2 | Within 2 WD of performing Consumption Data Comparison Check (3.6.9) | Notify the Registrant, and CDCA/HHDC of non-compliance. If relevant notify the MOA. If the visit was a Targeted Visit notify BSCCo. | TAA | Registrant, and HHDC/CDCA; MOA (if appropriate); BSCCo (for Targeted Audit only) | Specific details of non-compliance (Completed and signed Audit Schedule). | Online database or other agreed method |
3.8.3 | Within 1 WD of receiving notification in 3.8.1 and 3.8.2. | Inform the TAA that a non-compliance notification has been received. | Registrant | TAA | Acknowledgement. | Online database or other agreed method |
3.8.4 | Within 10 WD of receiving a non-compliance notification in 3.8.1 & 3.8.2. | (a) Where the Registrant, MOA, HHDC, CDCA agrees that Metering System is non-compliant; provide a rectification plan to the TAA or rectify the Metering System defects5 and inform the TAA of action taken. Proceed to Section 3.8.7. | Registrant, MOA, HHDC, CDCA, | TAA | Details of the Rectification action taken, or a rectification plan (Appendix 4.5.5 - BSCP27/05). | Online database or other agreed method |
| Or following 3.8.6. | (b) Where the Registrant or MOA disagrees with the non-compliances raised; inform the TAA and follow the query process set out in 3.9. | Registrant, MOA | TAA | Non-compliance appealed and reason for disagreement | Online database or other agreed method |
3.8.5 | On 11th WD after notifying a Registrant of non-compliance | Where a query or appeal has not been received, and no rectification details or plan are received from the Registrant, MOA, or HHDC/CDCA, send a reminder to the Registrant, MOA, and HHDC/CDCA, requesting a rectification plan or details of the rectification action taken. | TAA | Registrant, MOA or HHDC/CDCA | Details of non-compliance and request for rectification plan or details of the rectification action taken. | Online database or other agreed method |
3.8.6 | Within 1 WD of receiving the reminder detailed in 3.8.5. | Inform the TAA that a reminder notification has been received and proceed to 3.8.4. | Registrant, MOA and HHDC/ CDCA | TAA | Acknowledgement of reminder notification. | Online database or other agreed method |
3.8.7 | Within 3 WD of 3.8.6 | Where no rectification plan or details of the rectification action taken are received, the TAA will report the instances to BSCCo. | TAA | BSCCo |
| Email or as agreed |
|
| (a) The TAA will inform the Registrant, MOA, and HHDC/CDCA that they have failed to provide adequate rectification details and have been reported to BSCCo. | TAA | Registrant, MOA or HHDC/CDCA |
|
|
|
| (b) BSCCo will confirm to the Registrant that it is investigating the issue6. | BSCCo | Registrant |
|
|
3.8.8 | Within 2 WD of 3.8.4a or following 3.8.9a | Analyse the Information provided. | TAA |
|
| Internal process |
|
| (a) Where the Registrant, MOA or HHDC/CDCA has provided adequate information to show the rectification action is complete, close the non-compliance and notify the Registrant. MOA and HHDC/CDCA. Process ends. |
| Registrant, MOA and HHDC/CDCA |
| Online database or other agreed method |
|
| (b) Where the Registrant, MOA or HHDC/CDCA does not provide adequate information to show the rectification action is complete; or a complete rectification plan, notify the Registrant, MOA, and HHDC/CDCA with the reasons and proceed to 3.8.3. |
| Registrant, MOA and HHDC/CDCA |
| Online database or other agreed method |
|
| (c) Where the Registrant, MOA or HHDC/CDCA provides an adequate rectification plan, notify the Registrant and MOA and HHDC/CDCA that the plan is satisfactory. |
| Registrant, MOA and HHDC/CDCA |
| Online database or other agreed method |
3.8.9 | As appropriate for the milestones in the rectification plan. | Monitor completion of milestones in the rectification plan. Analyse the information required. | TAA |
|
| Internal process |
|
| (a) Where the milestones have been met provide confirmation to the Registrant, MOA, HHDC/CDCA, and BSCCo. If the final milestone has been met proceed to 3.8.8a. |
| Registrant, MOA, HHDC/CDCA and BSCCo |
| Online database or other agreed method |
|
| (b) Where the milestones have not been met or no information is received regarding the completion of milestones from the Registrant, MOA or HHDC/CDCA, Go to 3.8.7. | TAA |
|
| Online database or other agreed method |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.8A.1 | Within 2 WD of 3.6.1 and where a Category 1 Non Compliance has been identified | Request HH consumption data held by the HHDC/CDCA. | BSCCo | HHDC/CDCA | HH consumption data for the period affected by Category 1 Non Compliance. | Email or other agreed format |
3.8A.2 | Within 5 WD of 3.8A.1 | Provide HH consumption data requested in 3.8A.1 | HHDC, CDCA | BSCCo | HH consumption data for the period affected by Category 1 Non Compliance. | Email or other agreed format |
3.8A.3 | Within 2 WD of 3.8A.2 | Perform estimated metered net error materiality calculation. | BSCCo |
| Estimated metered net error materiality. | Online database or other agreed method |
Ref | When | Action | From | To | Information Required | Method |
3.9.1 | Following 3.8.4b | The Registrant, MOA, or HHDC/CDCA raises a query with the TAA. | Registrant MOA HHDC/CDCA | TAA | Party details, Contact details and Supporting information. | Online database or other agreed method |
3.9.2 | Within 5 WD of 3.9.1 | The TAA will review the information and record a summary of all discussions and information gathered. | TAA |
| A summary of all discussions and information gathered. | Online database or other agreed method |
3.9.3 | Within 5 WDs of 3.9.1 (and in parallel with 3.9.2) | The TAA will present its decision to the raising party. | TAA | Registrant MOA HHDC/CDCA | Supporting information. | Online database or other agreed method |
3.9.4 | Following 3.9.3 | The raising party will consider the TAAs decision, if agrees the TAA will leave the non-compliance open as it is considered valid. Go to 3.6. | Registrant MOA HHDC/CDCA | TAA |
| Online database or other agreed method |
3.9.5 | Following 3.9.3 | If the raising party disagrees with the TAAs decision, the TAA will initiate the query arbitration process (which escalates the decision process to a senior member of the TAA). | TAA |
|
| Internal process |
3.9.6 | Following 3.9.5 | The raising party will consider the TAAs escalated decision, if agrees the TAA will leave the non-compliance open as it is considered valid. Go to 3.8. | Registrant MOA HHDC/CDCA | TAA |
| Online database or other agreed method |
3.9.7 | Following 3.9.5 | If the raising party disagrees with the TAAs escalated decision the raising party may escalate the query to BSCCo for consideration. | Registrant MOA HHDC/CDCA | BSCCo | Supporting information. | Email or as agreed |
3.9.8 | Following 3.9.7 | BSCCo will consider the raising party’s issue and inform them of its decision. | BSCCo | Registrant MOA HHDC/CDCA |
| Email or as agreed |
3.9.9 | Following 3.9.8. | If the raising party disagrees with BSCCo’s decision the raising party may raise an appeal, to be considered by the PAB. If so, proceed to the appeal process (3.10). | Registrant MOA HHDC/CDCA |
|
| Online database or other agreed method |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.10.1 | Registrant raises an appeal | The Registrant raises an appeal against a specific non-compliance. | Registrant | TAA | Reasons why the non-compliance has been appealed. | Online database or other agreed method |
3.10.2 | Following 3.10.1 | The TAA notifies BSCCo that an appeal has been raised and provides all relevant information. | TAA | BSCCo | Reasons why the non-compliance has been appealed. Any information from the Query process. Any supporting evidence. | Online database or other agreed method |
3.10.3 | Within 20 WD of receipt of appeal. | BSCCo considers the grounds for the appeal and decides that: | BSCCo |
| Reasons why the non-compliance has been appealed. | Internal process |
|
| (a) The appeal is valid and withdraws the non-compliance and informs the Registrant of the decision and that the appeal is now closed. Process ends. |
| Registrant | Details of why the non-compliance has been removed. | Email or as agreed |
|
| (b) The appeal is not valid and informs the Registrant that the non-compliance will be upheld. |
| Registrant | Details of why non-compliance is still valid. | Email or as agreed |
3.10.4 | Following 3.10.3. | BSCCo directs the TAA to take any action required.
| BSCCo | TAA | Reasons why the non-compliance has been appealed. Details of why the non-compliance has been removed. Details of why non-compliance is still valid. | Email or as agreed |
3.10.5 | Within 5 WD of receiving notification in 3.10.4 | Registrant considers appeal decision. (a) If Registrant accepts decision; inform BSCCo. Proceed to 3.8.3. (b) If Registrant still disagrees with the non-compliance, acknowledge receipt of decision. Notify BSCCo that they wish to present appeal to the PAB7. The Registrant may request attendance at the next PAB meeting. | Registrant |
BSCCo
BSCCo | Reasons why the non-compliance has been upheld. Acknowledgement of receipt of appeal decision. Reasons why the non-compliance has been appealed. | Email or as agreed |
3.10.6 | Within 1 WD of receipt of the appeal details in 3.10.4 | Notify the TAA of appeal to PAB. | BSCCo | TAA | Reasons why the non-compliance has been appealed. | Email or as agreed |
3.10.7 | At next appropriate meeting of the PAB. | BSCCo reports the appeal details to the PAB for decision. | BSCCo | PAB | Details of non-compliance and details of why the non-compliance has been appealed by the Registrant | PAB Paper |
3.10.8 | At PAB meeting | PAB considers the grounds of the appeal and decides whether to uphold or withdraw the non-compliance. | PAB |
| Reasons why the non-compliance has been appealed, all relevant supporting information and the report from the TAA and BSCCo. | Internal Process |
|
| (a) The PAB decides that the appeal is valid and informs the relevant parties to withdraw the non-compliance. Process ends. | PAB via BSCCo | Registrant TAA | The PAB’s decision and reasons. | Email or as agreed |
|
| (b) The PAB decides that the appeal is not valid and informs the relevant parties to continue with the non-compliance procedure. Proceed to 3.8.3. | PAB via BSCCo | Registrant TAA | The PAB’s decision and reasons. | Email or as agreed |
REF | WHEN | ACTION | FROM | TO | INFORMATION REQUIRED | METHOD |
3.11.1 | Monthly | Provide BSCCo with a report of the results of all Inspection Visits and Desktop Audits completed in the previous month and details of all outstanding non-compliances and progress of these outstanding non-compliances. | TAA | BSCCo |
| Online database or other agreed method |
3.11.2 | On or before PAB paper day | At the discretion of the BSCCo, provide the PAB with details of Inspection Visits and Desktop Audits completed by the TAA in the previous month and details of all outstanding non-compliances. | BSCCo | PAB |
| PAB Paper |
3.11.3 | At the PAB meeting | Determine what action, if any, needs to be taken in respect of a non-compliant Registrant. The PAB may also choose to initiate the Removal of Qualification Process for a MOA and HHDC. | PAB |
| Details of Inspection Visits and Desktop Audits completed by the TAA in the previous month and details of all outstanding non-compliances. | Removal of Qualification Process is defined in BSCP537. |
To
From
Email address
Date
Time
MSID
Visit Ref
Site Name / Address
Attendees
Meter Test Certificates for all listed MSIDs
Test Certificates for all Measurement Transformers for all listed MSIDs
Commissioning documentation
Compensation calculations (including Transformer Losses, etc), on a circuit by circuit basis
Metering Equipment Alarm reporting procedure
And all other reasonable requests made by the TAA
To
From
Email address
MSID
Contact
Company
Telephone Number
TAA visit Reference
Meter Operator Agent Contact
Registrant Contact
LDSO Contact
Customer Contact
Telephone number
Email address
Category
Associated Rectification Action
Target date for completion
Key Milestones (e.g. MTDs provided by specific date)
Where the responsibility is for completing the action
To
From
Email address
Date
Time
MSID
Visit Ref
Site Name
3 “MOA” should be taken to apply to both SVA MOAs and CVA MOAs unless otherwise stated.
4 In the case of Inspection Visits to Metering Systems located offshore, the TAA shall provide a minimum of 90 WD notice. In such cases, where a visit has not taken place within 20 WD of the intended visit date, the TAA shall notify BSCCo, giving reasons for the failure. BSCCo may refer the matter to the Performance Assurance Board. In the case of Targeted Inspections, the TAA shall provide no more than 10 WD notice.
5 It should be noted that it is the responsibility of the Registrant to progress any non-compliances associated with a Settlement Metering System. However, the MOA can progress the rectification of a non-compliance at the request of the Registrant and will follow the actions of the Registrant detailed in this process.
6 This may result in escalation to the PAB.
7 The Panel have delegated authority to the PAB.
8 Where the LV CTs are of accuracy class 0.5 or below the TAA will not require the MOA to obtain the CT certificates and the error shall be deemed that of the accuracy class in both directions for the purpose of establishing the overall error.
9 The TAA is able to request any additional information in relation to any Metering System, and is not restricted to the Metering Systems which are being physically audited.